Optimized Design: Battery can represent a significant part of UPS budget in greenfield or brownfield projects. That’s why PESS RBC-02/06/12 is designed with a wide output DC voltage range to optimize:
-Number of battery cells.
-Battery capacity and therefore the price, as per the required autonomy.
-Various solutions to operate with the differing input voltage networks (nominal value, tolerance, frequency).
-Various LVD and Dropper configurations to get flexible design.
Make easy to replace complete power electronic parts of product thanks to modul-type design, easy maintenance
High MTBF above 100 000 hours with appropriate maintenance plan
Customizable fault and status 8 or 16 relays for enhanced interfacing whit existing DCS and SCADA systems
Thanks to modular design of power electronic control parts, specialized designs are possible with LVD, diode droppers or dc/dc converter regulators.
User friendly HMI Panel and Communication Software
Input | |
---|---|
AC voltage | 110 | 120 | 127 | 220 | 230 | 240 | 380 | 400 | 440 | 460 | 480 (+10%, -15%) |
Frequency | 50 or 60 Hz +-5% |
Neutral configuration | With or without neutral |
DPF (cos ϴ) | 1Ph>0.75 & 3Ph>0.9 (at full load) |
Power factor (PF) | 1Ph>0.7 & 3Ph>0.85 (at full load) |
Output | |
Nominal DC voltage | 24V | 48V | 110V | 125 | 220V | 360V | 384V |
Output DC voltage range | 20-30V | 40-60V | 90-150V | 100-160V | 200-300V | 240-450V | 320-480V |
Output voltage stability (in floating mode): Single system | +-1% |
Output voltage stability (in floating mode): Parallel system | +-2% |
Voltage ripple | <1% rms (without battery) |
Current limitation | 5% to 100% |
Battery | |
Type | Lead acid | Nickel cadmium |
Autonomy | Few minutes to hours |
Battery current limitation: Lead Acid battery | 0.1C |
Battery current limitation: Ni-Cd battery | 0.2C |
Battery room temperature compensation | 0.04V /1C degree per 12V battery, above and below 25C degree |
General | |
Dimension | Depends on the project |
IP protection | IP 20/21/42/54 (IEC60529) |
Cabinet color | RAL7035 or special |
Cooling | Forced with FANs |
Efficiency | 80-95% (depends on ratings) |
Noise (1m from unit) | 60-70% (depends on ratings) |
Operating temperature | 0-40 C degree |
Storage temperature | -20 to 70 C degree |
Relative humidity | <95 non-condensing |
Operating altitude | 1000m max. without derating |